TKBPXZ(L) Power Frequency Series Resonant Test System
Other name:Power frequency series resonance、Series resonance、Series resonant transformer
Specification Certificate of identification Service promise
Current limiting protection Power amplifier protection Voltage short circuit protection Open circuit protection Thermal protection of power amplifier
Note:Regarding product purchase, technical maintenance and other services, welcome to send email:
With the development of power system the capacity of running equipment is increasing. For example Thermal generator group the single capacity has exceeded 1000MW and hydrodynamo group the maximum capacity has reached 800MW. If traditional test equipment (power frequency test transformer) is used for the ac power frequency withstand Voltage test of these devices the regulator is very bulky because of the large test capacity required and the high-capacity test power supply is difficult to solve in the field so the field test is extremely inconvenient. The Power frequency withstand voltage tester host no matter from test Power supply capacity equipment weight the waveform and has advantages in such aspects as investment. The Power frequency withstand voltage tester host focuses on the potential of capacity of 250 mw and below hydrodynamo ac withstand voltage test of the design and manufacture.
1、Due to full compensation of resonant reactive power the power of power supply and equipment is less than 1/10 of the required capacity of the subject (1/q10); Small size and light weight with the same capacity large output capacity of the device and small power capacity required for configuration cheap convenient and safe operation.
2、Series resonance is actually a current filtering circuit so that the current passing through the subject is basically the fundamental current and the waveform distortion rate (THD) of the output voltage is very small which is superior to all existing ac voltage withstand equipment.
3、The short circuit current of the sample after flashover or breakdown is only less than 1/10 (1/Q) of the test current before short circuit which can effectively prevent the expansion of damage to the fault point after breakdown.
4、After flashover the arc will be automatically extinguished immediately. The long (number of seconds) process of restoring resonant state voltage after arc quenching is a steady-state establishment process and there is no danger of voltage overshoot and no danger of restoring overvoltage in microsecond millisecond transient process.
Rated output voltage | 0 ~ 60kV(AC RMS) and below |
output frequency | 50Hz |
Resonance voltage waveform | Pure sine wave waveform distortion rate ≤1% |
Work system | Full power conticontrol consolenuous working time of 1min |
quality factor | 10~40 |
Maximum test capacity | 3000kVA and below |
Working power supply | 380V±15%、Power frequency 50Hz |
Product model | control console | Voltage regulator | reactor(dry) | Excitation transformer(dry) | Voltage divider | Scope of application |
TKBPXZ(L)- 200kVA/25kV | 30kW | 30kVA(electric) | 200kVA/25kV Adjustable one | 30kVA dry | 30kV | hydrodynamo.0.4~1.0μF.(10kV/40MW) |
TKBPXZ(L)- 300kVA/50kV | 60kW | 60kVA(electric) | 300kVA/50kV Adjustable one | 60kVA oil-immersed | 50kV | Thermal generator.0.27~0.33μF.(20kV/300MW) |
TKBPXZ(L)- 600kVA/50kV | 60kW | 60kVA(electric) |
200kVA/50kV Adjustable one 400kVA/50kV Adjustable one |
60kVA oil-immersed | 50kV | Thermal generator.0.113~0.45μF.(20kV/600MW) |
TKBPXZ(L)- 1200kVA/50kV | 120kW | 120kVA(induction) |
200kVA/50kV Fixed two 800kVA/50kV Adjustable one |
120kVA oil-immersed | 50kV | hydrodynamo.0.6~1.8μF.(20kV/250MW) |
TKBPXZ(L)- 2750kVA/55kV | 300kW | 300kVA(induction) |
750kVA/55kV Fixed two 1250kVA/55kV Adjustable one |
120kVA oil-immersed | 60kV | hydrodynamo.1.6~3.3μF.(20kV/770MW) |
hydrodynamo | Rated Capacity(WM) | rated voltage(kV) | Phase capacitor(μF) |
72.5~85 | 10.5 | 0.694 | |
125~150 | / | 1.8~1.9 | |
300 | 15.75 | 1.7~2.5 | |
400 | 18.0 | 2~2.5 | |
600 | / | 2.1~2.5 |
Quality Keep Improving - Service Pursuing Perfection Pre-sales service commitment Provide professional consulting service; dedicated salesman and professional technical engineer to answer customer questions Ensure customer get the detailed information about the product in hand Reasonable price. Quotation stamped and confirmed by Manager
Welcome customers visit on-purchase service commitment The contract and the technical agreement to sign by both parties Being trustworthy, follow the requirements and ensure successful implementation of signed contracts and technical agreements Focus on communication, actively communicate with users, take notes of user’s questions and schedule, provide the necessary technical support. Move quick and efficient, professional on delivery, installation, debugging, training and others
After-sales service commitment Professional after-sales service department; ask and listen to customer’s feedback about the products and take records. Product guaranty: one year free warranty, life long maintenance, since the delivery of the product Provide solutions within 24 hours when there is problems feedback from customer. Professional research and development team.
Mobile station